Commissioning
Name Type Description Defaultvalue
Vendor REG_SZ NameofUPSmanufacturer "(none)"
Model REG_SZ UPSmodeldesignation ""
RunTaskEnable REG_DWORD Activates/deactivatestheconfigurationofthe
TaskSchedulershutdowntask:
0:=deactivated;
1:=activated;
othervaluesarenotpermissible;
0
TaskName REG_SZ NameoftheTaskSchedulershutdowntask.
TheBeckhoffUPSConfigurationdialog
generatesashutdowntaskwiththename:
"UPSSystemShutdownProgram".
""
TaskFolder REG_SZ PathtothefoldercontainingtheTask
Schedulershutdowntask.Implementedinthe
UPSsoftwarev3.0.0.10andhigher.Anempty
stringrepresentstherootfolder.
""
TaskCompatibility REG_DWORD TaskSchedulerv1.0compatibilitysettings.
ImplementedintheUPSsoftwarev3.0.0.10
andhigher:
0:=automatic,usesthelatestTask
Schedulerinterfaceversion
(atpresentv2.0);
1:=explicitlytheTaskSchedulerv1.0is
tobeused;
2:=explicitlytheTaskSchedulerv2.0is
tobeused;
othervaluesarenotpermissible;
0
RunTaskWait REG_DWORD Maximumrunningtime(executiontime)ofthe
shutdowntaskinseconds.Followingthe
expiryofthistimetheshutdowntaskis
stoppedandtheshutdowniscontinued.
ImplementedintheUPSsoftwarev3.0.0.8
andhigherandonlyunderWindowsVista,
W7,WES7(32and64bit).Witholder
operatingsystemsthistimecannotbe
changedandisfixedat30seconds.
30
ShutdownOnBatter
yEnable
REG_DWORD Activates/deactivatestheshutdownofthe
operatingsystemonacriticalalarm:
0:=deactivated;
1:=activated;
othervaluesarenotpermissible;
1
ShutdownOnBatter
yWait
REG_DWORD Maximumrunningtimeonbatteryvoltage
beforethecriticalalarminminutes.This
elementcanadoptavalueofbetween0and
720.Othervaluesarenotpermissible.
2
NotifyEnable REG_DWORD Activates/deactivatesthepowerfailmessages
totheloggedinuser:
0:=deactivated;
1:=activated;
othervaluesarenotpermissible;
0
TurnUPSOffEnable REG_DWORD Activates/deactivatestheswitchingoffofthe
UPSoutputvoltageaftertheshutdown:
0:=deactivated;
1:=activated(switchesoff);
1
CX210009x466 Version1.1