Mountingandwiring
Theterminalsareimplementedinspringforcetechnology.Connectthecablesasfollows:
1. Openaspringloadedterminalbyslightlypushingwithascrewdriverorarodintothesquareopening
abovetheterminal.
2. Thewirecannowbeinsertedintotheroundterminalopeningwithoutanyforce.
3. Theterminalclosesautomaticallywhenthepressureisreleased,holdingthewiresafelyand
permanently.
Wirecrosssection 0,5...2.5mm
2
AWG20…AWG14
Striplength 8...9mm 8.38mm
LED
Ifthepowersupplyunitisconnectedcorrectlyandthepowersupplyisswitchedon,thetwoupperLEDsin
theterminalprismaregreen.TheleftLED(Us)indicatestheCPUsupply.TherightLED(Up)indicatesthe
terminalsupply.TheotherLEDsindicatetheTerminalBusstatus.AdetaileddescriptionoftheLEDscanbe
foundinsection“LEDtroubleshooting”.
ULrequirements
WARNING
LossofULListing
InordertocomplywithULrequirements,theCXcontrollersmustnotbeconnectedtoun
limitedvoltagesources!
InordertocomplywithULrequirements,theCXcontrollersmayonlybeconnectedtosup
plyvoltages(24VDC)thatoriginatefrom:
a)anisolatedsourcethatisprotectedwithafuse(compliantwithUL248)of4Amax.,or
b)avoltagesourcethatiscompliantwithNECclass2.
AnNECclass2voltagesourcemustnotbeconnectedinseriesorparallelwithanother
NECclass2voltagesource!TheseULrequirementsapplytoallsupplyvoltagesforCX
controllers!
PEpowercontacts
Attention
Powercontact“PE”
The“PE”powercontactmustnotbeusedforotherpotentials.“PE"and“0V"(24Vsystem
supply)musthavethesamepotential(connectedinthecontrolcabinet).Thecablinginthe
controlcabinetmustcomplywithEN602041:2006PELVProtectiveExtraLowVoltage.
EN602041:2006section6.4.1:b):Onesideofthecircuitoronepointoftheenergysource
forthiscircuitmustbeconnectedtheprotectiveearthconductorsystem.
Attention
Interruptionofthepowersupply/switchingoff
Thedevicemaynotbeswitchedoffbydisconnectingtheground.The24Vlinemustal
waysbedisconnectedfirst,sinceotherwisecurrentmaycontinuetoflowviatheshielding,
dependingonthedevice.Anydeviceswithindependentpowersupplythatmaybecon
nected(e.g.aPanel)musthavethesamepotentialastheCXsystemfor“PE"and
“GND"(nopotentialdifference).Apotentialdifferencemayresultindamagetothecon
trollerandtheperiphery.