Product Overview
22 Embedded PC
CX1000-N005 connections
The system interface CX1000-N005 contains two RS422, RS485 interfaces, COM2 and COM3 (9 pin Sub-D plug
connector).
The maximum baud rate on both channels is 115 kBit.
COM interface (plug):
Pin assignment of the COM interface:
PIN Signal Type Description
2 TxD+ Data-Out + Transmit 422
3 RxD+ Data-In + Receive 422
5 GND Ground Ground
6 VCC VCC +5V
7 TxD- Data-Out - Transmit 422
8 RxD- Data-In - Receive 422
For RS 485 Pin 2 and 3 ( Data +) as well as Pin7 and 8 (Data -) have to be connected.
The pins not listed are not used.
Settings DIP switches RS485:
RS485 without Echo, End-Point ( Terminated) DEFAULT SETTING
DIP Status Function
1 off Echo on
2 on Echo off
3 on Auto send on
4 off Always send on
5 on Auto receive on
6 off Always receive on
7 on Term on
8 on Term on
RS485 with Echo, End-Point ( Terminated)
DIP Status Function
1 on Echo on
2 off Echo off
3 on Auto send on
4 off Always send on
5 off Auto receive on
6 on Always receive on
7 on Term on
8 on Term on